SV4050 ifmSVM12XXXD0KG/US-100

Vortex flow meter; Operating voltage [V] : 8...33 DC; Min. insulation resistance [MΩ] : 100; (500 V DC); Protection class : III; Power-on delay time [s] : < 2; Total number of outputs : 1; Output signal : analogue signal; Number of analogue outputs : 1; Analogue current output [mA] : 4...20; (Q [l/min] = 0,938 x (I - 4 mA)); Max. load [Ω] : < (Ub - 8 V) / 20 mA; Ub = 24 V: 800; Measuring range : 0.9...15 l/min: 0.133...2.21 m/s; Accuracy [K] : ± 0,3 ± 0,005 x T; Response time [s] : 0.5; Ambient temperature [°C] : -15...85; Storage temperature [°C] : -30...85; Cavitation : P(absolute) discharge / P(difference) > 5.5 to avoid cavitation; Materials : PA 6T; Materials (wetted parts) : ETFE; PA 6T; FKM; Tightening torque [Nm] : 12; Process connection : threaded connection G 1/2 DN8

Type
Flow sensors / flow meters
Connection
Connector: 1 x M12; Contacts: gold-plated
No. of inputs/outputs
Number of analogue outputs: 1
Current consumption
100 mA
Voltage supply
24 V
Display
Display unit: 6 x LED, green (l/min, m³/h, gpm, gph, °C, °F) | measured values: alphanumeric display, 4-digit | programming: alphanumeric display, 4-digit
Degree of protection
IP 65
Weight
65 g
Dimensions
104.5 x 32.5 x 113.6 mm