SA5000 ifmSAD10XDBFRKG/US-100

Flow sensor; Operating voltage [V] : 18...30 DC; Protection class : III; Reverse polarity protection : yes; Power-on delay time [s] : 10; Total number of outputs : 2; Output signal : switching signal; analogue signal; frequency signal; IO-Link; (configurable); Electrical design : PNP/NPN; Number of digital outputs : 2; Output function : normally open / normally closed; (parameterisable); Max. voltage drop switching output DC [V] : 2.5; Permanent current rating of switching output DC [mA] : 250; Number of analogue outputs : 1; Analogue current output [mA] : 4...20; (scalable); Max. load [Ω] : 350; Short-circuit protection : yes; Type of short-circuit protection : pulsed; Overload protection : yes; Frequency of the output [Hz] : 0...1000; Probe length L [mm] : 45; Operating mode : relative; absolutely liquid; absolutely gaseous; (absolute: reference measurement recommended); Note on factory setting : Operating mode: relative; Dynamic response T05 / T09 [s] : 1,5 (T09); (water; flow velocity: 0,3...3 m/s); Setting range [m/s] : 0.04...3; Greatest sensitivity [m/s] : 0.04...3; Setting range [m/s] : 0.04...6; Setting range [m/s] : 0...100; Greatest sensitivity [m/s] : 30...100; Setting range [m/s] : 0...200; Temperature drift [cm/s x 1/K] : 0,003 m/s x 1/K (< 20 °C; > 70 °C); Temperature gradient [K/min] : 100; Repeatability : 0,05 m/s; (water; flow velocity: 0,05...3 m/s); Accuracy : ± (7 % MW + 2 % MEW); (for relative mode in the range of maximum sensitivity under the following conditions: water: 20...70 °C; inlet length: 1.5 m; DN25 (DIN 2448); mounting position according to instructions; Accuracy can differ for other media and mounting positions.); Response time [s] : 0.5; (T09; water; glycol: 0,8 s; air: 7 s; oil: 1,8 s; each T09); Parameter setting options : hysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour; Communication interface : IO-Link; Transmission type : COM2 (38,4 kBaud); IO-Link revision : 1.1; SDCI standard : IEC 61131-9; Profiles : Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis; SIO mode : yes; Required master port type : A; Process data analogue : 2; Process data binary : 2; Min. process cycle time [ms] : 3; Supported DeviceIDs : Type of operation: DeviceID | Factory setting / ModE = (REL): 533 | ModE = (LIQU): 540 | ModE = (GAS): 547; Ambient temperature [°C] : -40...80; Storage temperature [°C] : -40...100; Materials : stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PBT-GF20; PBT-GF30; Materials (wetted parts) : stainless steel (1.4404 / 316L); Gasket: FKM; Process connection : threaded connection M18 x 1,5 internal thread

Connection
Connector: 1 x M12; Contacts: gold-plated
No. of inputs/outputs
Number of digital outputs: 2; Number of analogue outputs: 1
Current consumption
< 100 mA
Voltage supply
24 V
Display
Display unit: 6 x LED, green (%, m/s, l/min, m³/h, °C, 10³) | switching status: 2 x LED, yellow | measured values: alphanumeric display, red/green 4-digit
Degree of protection
IP 65; IP 67
Weight
314 g
Dimensions
Ø 58 / L = 80.2 mm