7SJ8042-5EB90-1FQ0 L0S SIEMENS7SJ80425EB901FQ0L0S

OVERCURRENT PROTECTION RELAY HOUSING 1/6 19", 4 X I, 3 X U, 7 BI, 8 BO, (2 CHANGEOVER) 1 LIVE STATUS CONTACT measuring inputs: Iph = 1 A / 5 A, IEE (sensitive) = 0.001 to 1.6 A/0.005 to 8 A rated auxiliary voltage: 60 V/ 110 V / 125 V/ 220 V DC, 115 V / 230 V AC flush-mounting housing, screw terminals region world, IEC/ANSI language English (language can be changed) front membrane standard system interface port B (device bottom side, rear) IEC 61850, 100 Mbit Ethernet, with integrated switch optical, double, LC connector without system interf., Port A measurement: fault recording functionality: overcurrent protection + overcurrent protection(PH50/51) I>, I>>,I>>>,IP ground-fault protection overcurrent protection ground (50N/51N): IE>, IE>>,IE>>>, IEP ground fault protection IEE>,IEE>>,IEP overload protection (49) trip-circuit supervision (74TC) circuit breaker failure protection (50BF) unbalanced-load protection (46) undercurrent supervision (37) lock out (86) supplementary functions: directional element phase voltage protection, frequency protection synchrocheck flexible protection functions (char. (*) without automatic reclosing without fault locator