7SJ8011-5EB20-1FA0 SIEMENS7SJ80115EB201FA0

OVERCURRENT PROTECTION RELAY HOUSING 1/6 19", 4 X I, 3 BI, 5 BO, (2 CHANGEOVER) 1 LIVE STATUS CONTACT measuring inputs: Iph = 1 A / 5 A, Ie = 1 A / 5 A rated auxiliary voltage: 60 V/ 110 V / 125 V/ 220 V DC, 115 V / 230 V AC flush-mounting housing, screw terminals region world, IEC/ANSI language English (language can be changed) front membrane standard system interface port B (device bottom side, rear) IEC60870-5-103 or DIGSI4/modem electrical RS485 without system interf., Port A measurement: fault recording functionality: overcurrent protection+ overcurrent protection PH(50/51) I>,I>>,I>>>,IP ground-fault protection overcurrent protection ground (50N/51N: IE>, IE>>,IE>>>, IEP ground fault/ground short circuit prot. IEE>.IEE>>,IEEP overload protection (49) trip-circuit supervision (74TC) circuit breaker failure protection (50BF), unbalanced-load protection (46) undercurrent supervision (37) lock out (86) parameter set switchover supervision functions circuit-breaker control flexible protection functions (characteristic key values f(*) without automatic reclosing without fault locator

Customs tariff number
85363010
Expected origin
DE
Weight
4.000 kg