MACX MCR-EX-SL-IDSI-I-SP Phoenix Contact ⍾ 2924032
Output signal conditioner - MACX MCR-EX-SL-IDSI-I-SP - 2924032; Ex i output signal conditioner, HART. Isolates and sends intrinsically safe 0/4-20 mA signals to a load (I/P converters, control valves, displays) in Ex areas. Electrical 3-way isolation, wire break recognition, SIL 2 in accordance with IEC 61508, spring-cage connection.
- Type
- Ex i signal conditioners with functional safety
- No. of channels
- 1
- Nominal supply voltage
- 24 V DC
- Load/output load current output
- < 800 Ω (20 mA)
- Degree of protection
- IP20 (not assessed by UL)
- Ambient temperature (operation)
- -20 °C ... 60 °C (Any mounting position)
- Dimensions
- 12.5 mm x 116 mm x 114.5 mm
- EAN