MACX MCR-EX-SL-IDSI-I Phoenix Contact2865405

Output signal conditioner - MACX MCR-EX-SL-IDSI-I - 2865405; Ex i output signal conditioner, HART Isolates and sends intrinsically safe 0/4-20 mA signals to a load (I/P converters, control valves, displays) in Ex areas. Electrical 3-way isolation, wire break recognition, SIL 2 in accordance with IEC 61508.

Type
Ex i signal conditioners with functional safety
No. of channels
1
Load/output load current output
< 800 Ω (20 mA)
Degree of protection
IP20 (not assessed by UL)
Ambient temperature (operation)
-20 °C ... 60 °C (Any mounting position)
Dimensions
12.5 mm x 112.5 mm x 114.5 mm
EAN
4046356160421