7MF4033-1BA10-1NC7-Z B21+C11+Y15+Y17+Y21 SIEMENS7MF40331BA101NC7ZB21C11Y15Y17Y21

SITRANS P DS III / P410, HART,4-20 mA transmitter for pressure Measuring cell filling silicone oil, normal cleaning Span: 0,01 ... 1 bar g (0.15 ... 14.5 psi g), overload limit 6 bar Diaphragm stainless steel, measuring cell stainless steel Process connection: female thread 1/2-14 npt Die-cast aluminium housing Standard design Explosion protection fm + csa Electric connection and cable inlet: cable gland 1/2-14 npt Housing cover with window (digital indicator visible, customized adjustment supplement Y21 required) Rating plate inscriptions in Englisch, pressure units in H2O resp. psi Quality inspection certificate (Factory calibration) to IEC 60770-2 Stainless steel tag plate (measuring point description) Max.16 character, specify in plain text: HART TAG (MAX. 8 CHARACTERS SPECIFY IN PLAIN TEXT) Adjustment digital indicator specify plain text Y21: mBar, bar, kpa, mpa,...

Typ
Przetworniki ciśnienia DSIII