7MF4033-1DA10-1AC7-Z A01+B11+C11+Y01+Y15+Y21 SIEMENS7MF40331DA101AC7ZA01B11C11Y01Y15Y21

SITRANS P DS III / P410, HART,4-20 mA transmitter for pressure Measuring cell filling silicone oil, normal cleaning Span: 0,16 ... 16 bar g (2.32 ... 232 psi g), overload limit 32 bar Diaphragm stainless steel, measuring cell stainless steel Process connection: female thread 1/2-14 npt Die-cast aluminium housing Standard design None explosion protection Electric connection and cable inlet: cable gland 1/2-14 npt Housing cover with window (digital indicator visible, customized adjustment supplement Y21 required) With steel mounting bracket Plate inscription: english Quality inspection certificate (Factory calibration) to IEC 60770-2 Range (linear characteristic) specify in plain text:, Y01:... to ...mBar,kpa,mpa,... Stainless steel tag plate (measuring point description) Max.16 character, specify in plain text: Adjustment digital indicator specify plain text Y21: mBar, bar, kpa, mpa,...