7MF4033-1DA00-1BB7-Z A01+B11+C11+E01+Y01+Y15+Y21 SIEMENS7MF40331DA001BB7ZA01B11C11E01Y01Y15Y21

SITRANS P DS III / P410, HART,4-20 mA transmitter for pressure Measuring cell filling silicone oil, normal cleaning Span: 0,16 ... 16 bar g (2.32 ... 232 psi g), overload limit 32 bar Diaphragm stainless steel, measuring cell stainless steel Process connection: connection shank G1/2 B to EN 837-1 Die-cast aluminium housing Standard design Explosion protection EEx ia Electric connection and cable inlet: cable gland M20 x 1.5 Housing cover with window (digital indicator visible, customized adjustment supplement Y21 required) With steel mounting bracket Plate inscription: english Test certificate according to standard IEC 60770-2 Dust explosion protection, usage in or at Zone 1D/2D, no gas approval. Instead Ex ia for gas only dust explosion protection, use in or at Zone 1D/2D Range (linear characteristic) specify in plain text:, Y01:... to ...mBar,kpa,mpa,... Stainless steel tag plate (measuring point description) Max.16 character, specify in plain text: Adjustment digital indicator specify plain text Y21: mBar, bar, kpa, mpa,...