3WL1108-2CB34-4AN4-Z K07+S01+S30 SIEMENS3WL11082CB344AN4ZK07S01S30

Fixed-mounted circuit breaker 3-pole, size I, IEC In=800A to 690V, AC50/60Hz Icu=55kA at 500V frnt.conn. top/bot. dual-hole Overcurrent release ETU 25 LSI protection adjustable 0.4-1 in Motorized/manual operating mechanism with spring charging motor AC 50/60 Hz 208-240 V or 220-250 V DC Activation AC 50/60 Hz 230 V, 220 V DC without 1st auxiliary release With 2nd auxiliary release "R", F3 Undervoltage, instant. 208-240 V AC, 220-250 V DC 4NO+4NC K07= Tripped signaling contact, 1 CO not possible with option F02 S01= CES locking device in OFF position (safe OFF/disconnector functionality) Disconnector condition IEC 60947-2 S30 = LOCKING DEVICE AGAINST OPENING OF CABINET