3WA1220-5AB30-2BA1-Z B16 SIEMENS3WA12205AB302BA1ZB16

Withdrawable circuit breaker without guide frame, IEC 60947-2, frame size 2, 3-poles, In=2000A up to 690V AC 50/60Hz, breaking capacity H Icu=100/85kA at 500/690V, Trip unit ETU300 LSI optimized for standard applica- tions, without display Protection LT, ST, INST, N-protection required an external N-sensor, incl. trip alarm switch (1xCO), without Com & metering function with manual and motorized operating mechanism (M) 24-30 V DC, Storage status and ready-to- close signaling switches, Auxiliary switches 2NO+2NC, Closing coil (CC) 100% OP 24-30 V DC, applicable for continuous duty, without Remote trip alarm reset coil (RR), without 2nd shunt trip, Shunt trip (ST) 100% OP 24-30 V DC, suitable for continuous duty, Option B16 = Option plug with reduced rated current In= 1600 A, rated current In < In max.,

Type
3WA Circuit breakers
Customs tariff number
85362090
Expected origin
CZ
Weight
47.969