3WA1120-4AC01-8SL1 SIEMENS3WA11204AC018SL1

Fixed-mounted circuit breaker IEC 60947-2, frame size 1, 3-poles, In=2000A up to 690V AC 50/60Hz, breaking capacity M Icu=85/66kA at 500/690V, Trip unit ETU300 LSIG optimized for standard applica- tions, without display Protection LT, ST, INST, GF, N-protection required an external N-sensor, incl. trip alarm switch (1xCO), rear connection vertical, without Com & metering function with manual and motorized operating mechanism (M) 208-240 V AC / 220-250 V DC, Storage status and ready-to- close signaling switches, Auxiliary switches 4NO+4NC, Closing coil (CC) 5% OP 208-240 V AC / 220-250 V DC, for momentary duty, Remote trip alarm reset (RR) 208-240 V AC / 220-250 V DC for momentary duty, Undervoltage release (UVR) instantaneous (0,08 s) and short-delay (0,2 s), 24 V DC, Shunt trip (ST) 100% OP 24-30 V DC, suitable for continuous duty,

Type
3WA Circuit breakers
Customs tariff number
85362090
Expected origin
CZ
Weight
39.100